ME-Spec

1.SCOPE

This specification applies to fiberglass outdoor pad mount modular enclosures. Unit shall be designed for mounting on a concrete pad by means of an internal flange completely around the base.
Enclosures shall be in complete conformance with ANSI C57.12.28, Pad Mount Equipment Enclosure Integrity Standard.

2.0 CONTRUCTION

  • Fiberglass laminate shall be 1/4” nominal thickness except where local reinforcement is required.
  • Fiberglass shall not support combustion and be self extinguishing.
  • Enclosure exterior shall be gelcoated to .014 inch nominal thickness and be manufacturer’s standard willow green, munsell green, and light gray colors.
  • Locking device shall be three point latch type with padlocking provisions

 

  • All hardware shall be made of stainless steel.
  • Enclosure shall be removable without disturbing enclosed equipment.
  • A stainless steel identification plate shall be affixed outside the enclosure which identifies the manufacturer, model number of the equipment, and date of manufacture.
  • Stainless steel louvers shall be provided with stainless steel screen baffle for adequate air flow and heat dissipation as required for enclosed equipment.

3.0 TESTING & STANDARDS

  • Certified test data for the structural standards of finished laminate shall be made available upon request.
  • The enclosure shall meet or exceed ANSI C57.12.28 Pad Mount Equipment Enclosure Integrity Standard.