1.SCOPE
This specification applies to fiberglass outdoor pad mount modular enclosures. Unit shall be designed for mounting on a concrete pad by means of an internal flange completely around the base.
Enclosures shall be in complete conformance with ANSI C57.12.28, Pad Mount Equipment Enclosure Integrity Standard.
2.0 CONTRUCTION
- Fiberglass laminate shall be 1/4” nominal thickness except where local reinforcement is required.
- Fiberglass shall not support combustion and be self extinguishing.
- Enclosure exterior shall be gelcoated to .014 inch nominal thickness and be manufacturer’s standard willow green, munsell green, and light gray colors.
- Locking device shall be three point latch type with padlocking provisions
|
- All hardware shall be made of stainless steel.
- Enclosure shall be removable without disturbing enclosed equipment.
- A stainless steel identification plate shall be affixed outside the enclosure which identifies the manufacturer, model number of the equipment, and date of manufacture.
- Stainless steel louvers shall be provided with stainless steel screen baffle for adequate air flow and heat dissipation as required for enclosed equipment.
3.0 TESTING & STANDARDS
- Certified test data for the structural standards of finished laminate shall be made available upon request.
- The enclosure shall meet or exceed ANSI C57.12.28 Pad Mount Equipment Enclosure Integrity Standard.
|